10
Advant Controller 31 / Issued: 07.99
Hardware 07 KP 93 R1161
8 .3
1.5.5 Mechanical data
Mounting on DIN rail in accordance with DIN EN 5002235, 15 mm deep.
The DIN rail is located in the middle between the upper
and the lower edges of the module.
Fastening by screws using 4 M4 screws.
Width x height x depth 140 x 120 x 85 mm
Wiring method by removeable terminal blocks with screw-type
terminals, max. 2.5 mm
2
Weight 450 g
Dimensions for mounting see the following drawing
1.5.6 Mounting hints
Mounting position vertical, terminals above and below
Cooling The natural convection cooling must not hindered by
cable ducts or other material mounted in the switch-
gear cabinet.
The device is 85 mm deep. The interface connectors COM3 and COM4 are set deeper so that the mounting
depth required does not become any larger even with detachable interface cables. If, however, a DIN rail is used,
the mounting depth is increased by the overall depth of the rail.
Fig. 11: Dimensions of the communication processor module 07 KP 93,
front view, the dimensions for assembly bore holes are printed in bold
All dimensions in mm.
5
94
94
120
65
130
140
65
111
75
20